EPM

Note

This page is generated by python script generate_cet.py.

Back to table

Commands

disable

Description: Transition from state Enabled to Disabled.

EFDB_Topic:

SALGeneric_command_disable

Category:

csc

enable

Description: Transition from state Disabled to Enabled.

EFDB_Topic:

SALGeneric_command_enable

Category:

csc

exitControl

Description: Transition from state Standby to Offline. Most CSCs will quit, but CSCs that support the enterControl command will keep running.

EFDB_Topic:

SALGeneric_command_exitControl

Category:

csc

setLogLevel

Description: Set the logging level.

EFDB_Topic:

SALGeneric_command_setLogLevel

Category:

csc

level

IDL_Type:

int

Units:

unitless

Description: Logging level, as a Python logging level: error=40, warning=30, info=20, debug=10.

subsystem

IDL_Type:

string

Units:

unitless

Description: If this CSC itself has sub-ordinate components, they may be listed here. An empty string means the setting applies to all such sub-ordinate components, or just to this CSC itself.

standby

Description: Transition from state Offline/Available, Disabled or Fault to Standby.

EFDB_Topic:

SALGeneric_command_standby

Category:

csc

start

Description: Transition from state Standby to Disable, in a specified configuration.

EFDB_Topic:

SALGeneric_command_start

Category:

csc

configurationOverride

IDL_Type:

string

Units:

unitless

Description:

Configuration override in the form [{name}][:{version}]. For salobj-based CSCs: name is a filename with “.yaml” suffix and version is a git hash; for example:

  • “foo.yaml” specifies just a file. Two or three config files are loaded: “_init.yaml”, “_{site}.yaml” (if present), and “foo.yaml”.

  • “:37bf936” specifies just a git hash. One or two config files are loaded from the specified git commit: “_init.yaml” and “_{site}.yaml” (if present.

  • “bar.yaml:HEAD~2” specifies both a file and a git hash. Two or three config files are read from the specified git commit: “_init.yaml”, “_{site}.yaml” (if present), and “bar.yaml”.

Events

configurationApplied

Description: Information about this CSC’s current configuration overrides.

EFDB_Topic:

SALGeneric_logevent_configurationApplied

Category:

configurable

configurations

IDL_Type:

string

Units:

unitless

Description: A comma-separated list of configurations applied. If configuration comes from a clone of a git repo, or similar directory, then it will be a list of file names, without the file extension. Ignore whitespace after commas.

version

IDL_Type:

string

Units:

unitless

Description: Version of the configuration source. For a clone of a git repo it will be a git hash.

url

IDL_Type:

string

Units:

unitless

Description: URL of the configuration source. For a clone of a git repo this will be a file URL. For a database it will be a standard database URL. This should always match the same-named field in configurationsAvailable.

schemaVersion

IDL_Type:

string

Units:

unitless

Description: Version of config schema used by this CSC. For a configuration git repo, this is the name of a folder in the config package, and is typically something like “v1”. This should always match the same-named field in configurationsAvailable.

otherInfo

IDL_Type:

string

Units:

unitless

Description: A comma-separated list of event topics (without the logevent prefix) used to publish the entire set of configuration parameters loaded by this CSC, and any other pertinent information. Ignore whitespace after commas.

configurationsAvailable

Description: Available configuration overrides for this CSC.

EFDB_Topic:

SALGeneric_logevent_configurationsAvailable

Category:

configurable

overrides

IDL_Type:

string

Units:

unitless

Description: Available overrides as a comma-separated list. Each entry is a possible value of the configurationOverride field of the start command. Ignore whitespace after commas.

version

IDL_Type:

string

Units:

unitless

Description: Version of the configuration source. For a clone of a git repo it will be a git hash.

url

IDL_Type:

string

Units:

unitless

Description: URL of the configuration source. For a clone of a git repo this will be a file URL. For a database it will be a standard database URL.

schemaVersion

IDL_Type:

string

Units:

unitless

Description: Version of config schema used by this CSC. For a configuration git repo, this is the name of a folder in the config package, and is typically something like “v1”.

errorCode

Description: Output when this CSC goes into the Fault state as an explanation of the problem.

EFDB_Topic:

SALGeneric_logevent_errorCode

Category:

csc

errorCode

IDL_Type:

long

Units:

unitless

Description: A numeric error code.

errorReport

IDL_Type:

string

Units:

unitless

Description: An string providing detailed information about the error.

traceback

IDL_Type:

string

Units:

unitless

Description: An optional stack trace of the error condition.

heartbeat

Description: Event output at regular intervals (typcally once per second) to show that the SAL component is alive.

EFDB_Topic:

SALGeneric_logevent_heartbeat

Category:

mandatory

heartbeat

IDL_Type:

boolean

Units:

unitless

Description: Deprecated field that you should ignore.

logLevel

Description: Current logging level.

EFDB_Topic:

SALGeneric_logevent_logLevel

Category:

mandatory

level

IDL_Type:

int

Units:

unitless

Description: Current logging level, a Python logging level: error=40, warning=30, info=20, debug=10.

subsystem

IDL_Type:

string

Units:

unitless

Description: If this CSC itself has sub-ordinate components, they may be listed here. An empty string means the setting applies to all such sub-ordinate components, or just to this CSC itself.

logMessage

Description: A log message.

EFDB_Topic:

SALGeneric_logevent_logMessage

Category:

mandatory

name

IDL_Type:

string

Units:

unitless

Description: Log name.

level

IDL_Type:

int

Units:

unitless

Description: Message level, a Python logging level: error=40, warning=30, info=20, debug=10.

message

IDL_Type:

string

Units:

unitless

Description: Log message.

traceback

IDL_Type:

string

Units:

unitless

Description: Exception traceback; “” if not an exception.

filePath

IDL_Type:

string

Units:

unitless

Description: Path to source file.

functionName

IDL_Type:

string

Units:

unitless

Description: Function or method name.

lineNumber

IDL_Type:

long

Units:

unitless

Description: Line number in the file specified by filePath.

process

IDL_Type:

long

Units:

unitless

Description: Process ID.

timestamp

IDL_Type:

double

Units:

second

Description: The time at which the condition being reported was observed (TAI unix seconds). 0 if unspecified.

simulationMode

Description: Current simulation mode.

EFDB_Topic:

SALGeneric_logevent_simulationMode

Category:

csc

mode

IDL_Type:

int

Units:

unitless

Description: Current simulation mode; 0 for normal operation (no simulation); other supported values are specific to each CSC.

softwareVersions

Description: Current versions of software in use by CSC.

EFDB_Topic:

SALGeneric_logevent_softwareVersions

Category:

mandatory

salVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: This is the current version of SAL generation.

xmlVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: This is the current version of CSC XML.

openSpliceVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: This is the current version of OpenSplice.

cscVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: The software version of this CSC.

subsystemVersions

IDL_Type:

string

Units:

unitless

Description: A comma delimited list of key=value pairs relating subsystem name (key) to its version number (value). This may be left blank if there are no subsystems within this CSC.

summaryState

Description: Current summary state of this CSC.

EFDB_Topic:

SALGeneric_logevent_summaryState

Category:

csc

summaryState

IDL_Type:

long

Units:

unitless

Description: High level state machine state identifier.

Telemetry

BatteryStatus:
  • Charging=1

  • Discharging=2

  • Floating=3

  • Resting=4

OnOff:
  • ON=1

  • OFF=2

pdu

Description: Telemetry for Netbooter PDU devices.

EFDB_Topic:

EPM_pdu

systemDescription

IDL_Type:

string

Units:

unitless

Description: The value of the SNMP System Description field.

acCurrentDraw

IDL_Type:

float

Units:

A

Description: AC current draw.

acMaxDraw

IDL_Type:

float

Units:

A

Description: AC maximum current draw detected.

powerOutletStatus

IDL_Type:

int

Units:

unitless

Count:

2

Description: Power Outlet Status.

scheiderPm5xxx

Description: Telemetry for Scheider PM5XXX devices.

EFDB_Topic:

EPM_scheiderPm5xxx

systemDescription

IDL_Type:

string

Units:

unitless

Description: The value of the SNMP System Description field.

serialNumber

IDL_Type:

string

Units:

unitless

Description: PM556x - Unit Serial Number

measuredLineVoltageVan

IDL_Type:

float

Units:

V

Description: Measured Line Voltage - Van - (Volts)

measuredLineVoltageVbn

IDL_Type:

float

Units:

V

Description: Measured Line Voltage - Vbn - (Volts)

measuredLineVoltageVcn

IDL_Type:

float

Units:

V

Description: Measured Line Voltage - Vcn - (Volts)

measuredLineVoltageVab

IDL_Type:

float

Units:

V

Description: Measured Line Voltage - Vab - (Volts)

measuredLineVoltageVbc

IDL_Type:

float

Units:

V

Description: Measured Line Voltage - Vbc - (Volts)

measuredLineVoltageVca

IDL_Type:

float

Units:

V

Description: Measured Line Voltage - Vca - (Volts)

loadCurrentA

IDL_Type:

float

Units:

A

Description: Measured Load Current - Phase A - (Amps)

loadCurrentB

IDL_Type:

float

Units:

A

Description: Measured Load Current - Phase B - (Amps)

loadCurrentC

IDL_Type:

float

Units:

A

Description: Measured Load Current - Phase C - (Amps)

neutralCurrent

IDL_Type:

float

Units:

A

Description: Measured Neutral Current - (Amps)

systemFrequency

IDL_Type:

float

Units:

Hz

Description: Measured System Frequency (Hz)

activePowerA

IDL_Type:

float

Units:

kW

Description: Active Power - Phase A - (kW)

activePowerB

IDL_Type:

float

Units:

kW

Description: Active Power - Phase B - (kW)

activePowerC

IDL_Type:

float

Units:

kW

Description: Active Power - Phase C - (kW)

reactivePowerA

IDL_Type:

float

Units:

kW

Description: Reactive Power - Phase A - (kVar)

reactivePowerB

IDL_Type:

float

Units:

kW

Description: Reactive Power - Phase B - (kVar)

reactivePowerC

IDL_Type:

float

Units:

kW

Description: Reactive Power - Phase C - (kVar)

apparentPowerA

IDL_Type:

float

Units:

kW

Description: Apparent Power - Phase A - (kVA)

apparentPowerB

IDL_Type:

float

Units:

kW

Description: Apparent Power - Phase B - (kVA)

apparentPowerC

IDL_Type:

float

Units:

kW

Description: Apparent Power - Phase C - (kVA)

powerFactorA

IDL_Type:

float

Units:

unitless

Description: Power Factor - Phase A

powerFactorB

IDL_Type:

float

Units:

unitless

Description: Power Factor - Phase B

powerFactorC

IDL_Type:

float

Units:

unitless

Description: Power Factor - Phase C

displacementPowerFactorA

IDL_Type:

float

Units:

unitless

Description: Displacement Power Factor - Phase A

displacementPowerFactorB

IDL_Type:

float

Units:

unitless

Description: Displacement Power Factor - Phase B

displacementPowerFactorC

IDL_Type:

float

Units:

unitless

Description: Displacement Power Factor - Phase C

totalPowerFactor

IDL_Type:

float

Units:

unitless

Description: Total Power Factor - Phase (A, B, C)

totalDisplacementPowerFactor

IDL_Type:

float

Units:

unitless

Description: Total Displacement Power Factor - Phase (A, B, C)

totalActivePower

IDL_Type:

float

Units:

kW

Description: Total Active Power - Phase (A,B,C) - (kW)

totalReactivePower

IDL_Type:

float

Units:

kW

Description: Total Reactive Power - Phase (A,B,C) - (kVar)

totalApparentPower

IDL_Type:

float

Units:

kW

Description: Total Apparent Power - Phase (A,B,C) - (kVA)

activeEnergyDelivered

IDL_Type:

float

Units:

J

Description: Accumulated Energy - Active Energy Delivered - (Wh)

reactiveEnergyDelivered

IDL_Type:

float

Units:

J

Description: Accumulated Energy - Reactive Energy Delivered - (VARh)

apparentEnergyDelivered

IDL_Type:

float

Units:

J

Description: Accumulated Energy - Apparent Energy Delivered - (VAh)

resetDateTime

IDL_Type:

string

Units:

unitless

Description: Accumulated Energy - Date /Time of Last Reset

xups

Description: Telemetry for XUPS devices.

EFDB_Topic:

EPM_xups

systemDescription

IDL_Type:

string

Units:

unitless

Description: The value of the SNMP System Description field.

batteryCapacity

IDL_Type:

float

Units:

unitless

Description: Battery percent charge.

batteryTimeRemaining

IDL_Type:

float

Units:

s

Description: Battery run time in seconds before UPS turns off due to low battery.

batteryVoltage

IDL_Type:

float

Units:

V

Description: Battery voltage as reported by the UPS meters.

envAmbientTemp

IDL_Type:

float

Units:

deg_C

Description: The reading of the ambient temperature in the vicinity of the UPS or SNMP agent.

batteryCurrent

IDL_Type:

float

Units:

A

Description: Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.

inputCurrent

IDL_Type:

float

Units:

A

Count:

3

Description: The measured input current from the UPS meters in amps.

inputPower

IDL_Type:

float

Units:

W

Count:

3

Description: The measured input real power in watts.

inputVoltage

IDL_Type:

float

Units:

V

Count:

3

Description: The measured input voltage from the UPS meters in volts.

inputFrequency

IDL_Type:

float

Units:

Hz

Description: The utility line frequency in tenths of Hz.

outputCurrent

IDL_Type:

float

Units:

A

Count:

3

Description: The measured UPS output current in amps.

outputPower

IDL_Type:

float

Units:

W

Count:

3

Description: The measured real output power in watts.

outputVoltage

IDL_Type:

float

Units:

V

Count:

3

Description: The measured output voltage from the UPS metering in volts.

outputFrequency

IDL_Type:

float

Units:

Hz

Description: The measured UPS output frequency in tenths of Hz.

outputLoad

IDL_Type:

float

Units:

unitless

Description: The UPS output load in percent of rated capacity.

bypassVoltage

IDL_Type:

float

Units:

V

Count:

3

Description: The measured UPS bypass voltage in volts.

bypassFrequency

IDL_Type:

float

Units:

Hz

Description: The bypass frequency in tenths of Hz.

batteryAbmStatus

IDL_Type:

int

Units:

unitless

Description: Gives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done.