MTM1M3TS

Note

This page is generated by python script generate_cet.py.

Back to table

Commands

applySetpoint

Description: Set new setpoint target for mirror temperature.

EFDB_Topic:

MTM1M3TS_command_applySetpoint

setpoint

IDL_Type:

float

Units:

deg_C

Description: Temperature setpoint to apply

coolantPumpFrequency

Description:

Sets coolant pump target frequency. 0 or negative values stops the pump. Pump is started if positive value is provided and it’s not running.

EFDB_Topic:

MTM1M3TS_command_coolantPumpFrequency

targetFrequency

IDL_Type:

float

Units:

Hz

Description: Coolant pump target frequency.

coolantPumpPower

Description: Turns power for coolant pump. Controls cRIO slot 5 SSR.

EFDB_Topic:

MTM1M3TS_command_coolantPumpPower

power

IDL_Type:

boolean

Units:

unitless

Description: Apply power to coolant pump, true=on, false=off.i Slot 5, Channel 2.

coolantPumpReset

Description: Resets coolant pump motor controller errors.

EFDB_Topic:

MTM1M3TS_command_coolantPumpReset

coolantPumpStart

Description: Start (run) the glycol coolant pump.

EFDB_Topic:

MTM1M3TS_command_coolantPumpStart

coolantPumpStop

Description: Stops the glycol coolant pump.

EFDB_Topic:

MTM1M3TS_command_coolantPumpStop

fanCoilsHeatersPower

Description: Turns power for fan coils/heaters. Controls cRIO slot 5 SSR.

EFDB_Topic:

MTM1M3TS_command_fanCoilsHeatersPower

power

IDL_Type:

boolean

Units:

unitless

Description: Apply power to Fan Coils/Heaters. true=on, false=off. Slot 5, Channel 0

heaterFanDemand

Description: Sets thermal unit heater PWM and fan RPM demand values. Command code 88 (0x58).

EFDB_Topic:

MTM1M3TS_command_heaterFanDemand

heaterPWM

IDL_Type:

byte

Units:

unitless

Count:

96

Description: Heater PWM demand. 0-255, where 255 equals 100%.

fanRPM

IDL_Type:

byte

Units:

unitless

Count:

96

Description: Fan RPM demand value. 0-255, where 255 equals 2550 RPM.

setEngineeringMode

Description: Enters and leaves engineering mode.

EFDB_Topic:

MTM1M3TS_command_setEngineeringMode

enableEngineeringMode

IDL_Type:

boolean

Units:

unitless

Description: Enable engineering mode.

setMixingValve

Description: Sets mixing valve position. Controls AO0 at slot 2.

EFDB_Topic:

MTM1M3TS_command_setMixingValve

mixingValveTarget

IDL_Type:

float

Units:

%

Description: Mixing valve commanded position.

disable

Description: Transition from state Enabled to Disabled.

EFDB_Topic:

SALGeneric_command_disable

Category:

csc

enable

Description: Transition from state Disabled to Enabled.

EFDB_Topic:

SALGeneric_command_enable

Category:

csc

exitControl

Description: Transition from state Standby to Offline. Most CSCs will quit, but CSCs that support the enterControl command will keep running.

EFDB_Topic:

SALGeneric_command_exitControl

Category:

csc

setLogLevel

Description: Set the logging level.

EFDB_Topic:

SALGeneric_command_setLogLevel

Category:

csc

level

IDL_Type:

int

Units:

unitless

Description: Logging level, as a Python logging level: error=40, warning=30, info=20, debug=10.

subsystem

IDL_Type:

string

Units:

unitless

Description: If this CSC itself has sub-ordinate components, they may be listed here. An empty string means the setting applies to all such sub-ordinate components, or just to this CSC itself.

standby

Description: Transition from state Offline/Available, Disabled or Fault to Standby.

EFDB_Topic:

SALGeneric_command_standby

Category:

csc

start

Description: Transition from state Standby to Disable, in a specified configuration.

EFDB_Topic:

SALGeneric_command_start

Category:

csc

configurationOverride

IDL_Type:

string

Units:

unitless

Description:

Configuration override in the form [{name}][:{version}]. For salobj-based CSCs: name is a filename with “.yaml” suffix and version is a git hash; for example:

  • “foo.yaml” specifies just a file. Two or three config files are loaded: “_init.yaml”, “_{site}.yaml” (if present), and “foo.yaml”.

  • “:37bf936” specifies just a git hash. One or two config files are loaded from the specified git commit: “_init.yaml” and “_{site}.yaml” (if present.

  • “bar.yaml:HEAD~2” specifies both a file and a git hash. Two or three config files are read from the specified git commit: “_init.yaml”, “_{site}.yaml” (if present), and “bar.yaml”.

Enumerations

SummaryStates:
  • DisabledState=1

  • EnabledState=2

  • FaultState=3

  • OfflineState=4

  • StandbyState=5

Events

appliedSetpoint

Description: Current target temperature setpoint.

EFDB_Topic:

MTM1M3TS_logevent_appliedSetpoint

setpoint

IDL_Type:

float

Units:

deg_C

Description: Applied setpoint.

enabledILC

Description: Currently enabled ILCs.

EFDB_Topic:

MTM1M3TS_logevent_enabledILC

enabled

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: True if this fan unit is enabled.

engineeringMode

Description: Is the system in engineering mode, allowing wider range of commands than non-engineering mode?

EFDB_Topic:

MTM1M3TS_logevent_engineeringMode

engineeringMode

IDL_Type:

boolean

Units:

unitless

Description: True if engineering mode is engaged.

flowMeterMPUStatus

Description: Flow meter MPU status and warnings. Send when errors are detected.

EFDB_Topic:

MTM1M3TS_logevent_flowMeterMPUStatus

instructionPointer

IDL_Type:

int

Units:

unitless

Description: Current MPU instruction pointer.

outputCounter

IDL_Type:

int

Units:

unitless

Description: Current MPU output counter.

inputCounter

IDL_Type:

int

Units:

unitless

Description: Current MPU input counter.

outputTimeouts

IDL_Type:

int

Units:

unitless

Description: Current MPU output timeouts counter.

inputTimeouts

IDL_Type:

int

Units:

unitless

Description: Current MPU input timeouts counter.

instructionPointerOnError

IDL_Type:

int

Units:

unitless

Description: Current MPU instruction pointer when error was detected.

writeTimeout

IDL_Type:

int

Units:

unitless

Description: Current MPU write timeout.

readTimeout

IDL_Type:

int

Units:

unitless

Description: Current MPU read timeout.

errorCode

IDL_Type:

int

Units:

unitless

Description: MPU error code.

glycolPumpMPUStatus

Description: Glycol pump MPU status and warnings. Send when errors are detected.

EFDB_Topic:

MTM1M3TS_logevent_glycolPumpMPUStatus

instructionPointer

IDL_Type:

int

Units:

unitless

Description: Current MPU instruction pointer.

outputCounter

IDL_Type:

int

Units:

unitless

Description: Current MPU output counter.

inputCounter

IDL_Type:

int

Units:

unitless

Description: Current MPU input counter.

outputTimeouts

IDL_Type:

int

Units:

unitless

Description: Current MPU output timeouts counter.

inputTimeouts

IDL_Type:

int

Units:

unitless

Description: Current MPU input timeouts counter.

instructionPointerOnError

IDL_Type:

int

Units:

unitless

Description: Current MPU instruction pointer when error was detected.

writeTimeout

IDL_Type:

int

Units:

unitless

Description: Current MPU write timeout.

readTimeout

IDL_Type:

int

Units:

unitless

Description: Current MPU read timeout.

errorCode

IDL_Type:

int

Units:

unitless

Description: MPU error code.

glycolPumpStatus

Description: Glycol pump status.

EFDB_Topic:

MTM1M3TS_logevent_glycolPumpStatus

ready

IDL_Type:

boolean

Units:

unitless

Description: True if the pump can be started.

running

IDL_Type:

boolean

Units:

unitless

Description: True if the pump is running.

forwardCommanded

IDL_Type:

boolean

Units:

unitless

Description: True if pump motor is commanded to run forward, false for backward command.

forwardRotating

IDL_Type:

boolean

Units:

unitless

Description: True if pump motor is rotating forward, false for backward rotation.

accelerating

IDL_Type:

boolean

Units:

unitless

Description: True if motor is accelerating.

decelerating

IDL_Type:

boolean

Units:

unitless

Description: True if motor is decelerating.

faulted

IDL_Type:

boolean

Units:

unitless

Description: True if motor faulted.

mainFrequencyControlled

IDL_Type:

boolean

Units:

unitless

Description: True if main frequency is controlled by the active communication.

operationCommandControlled

IDL_Type:

boolean

Units:

unitless

Description: True if pump motor operation is controlled by the active communication.

parametersLocked

IDL_Type:

boolean

Units:

unitless

Description: True if pump motor parameters are locked.

errorCode

IDL_Type:

int

Units:

unitless

Description: Motor controller error code. Please see VFD documentation for details.

mixingValveSettings

Description: Mixing Valve settings.

EFDB_Topic:

MTM1M3TS_logevent_mixingValveSettings

commandingFullyClosed

IDL_Type:

float

Units:

mA

Description: Raw value at which is mixing valve fully closed.

commandingFullyOpened

IDL_Type:

float

Units:

mA

Description: Raw value at which is mixing valve fully opened.

positionFeedbackFullyClosed

IDL_Type:

float

Units:

V

Description: Voltage level signalling fully closed mixing valve.

positionFeedbackFullyOpened

IDL_Type:

float

Units:

V

Description: Voltage level signalling fully opened mixing valve.

powerStatus

Description: Power status.

EFDB_Topic:

MTM1M3TS_logevent_powerStatus

fanCoilsHeatersCommandedOn

IDL_Type:

boolean

Units:

unitless

Description: True if Fan Coils/Heaters power bus commanded on.

fanCoilsHeatersOn

IDL_Type:

boolean

Units:

unitless

Description: True if Fan Coils/Heaters are on.

coolantPumpCommandedOn

IDL_Type:

boolean

Units:

unitless

Description: True if Coolant Pump commanded on.

coolantPumpOn

IDL_Type:

boolean

Units:

unitless

Description: True if Coolant Pump is on.

thermalInfo

Description: ILC information - position, address,..

EFDB_Topic:

MTM1M3TS_logevent_thermalInfo

referenceId

IDL_Type:

short

Units:

unitless

Count:

96

Description: Thermal ILC reference id.

modbusAddress

IDL_Type:

short

Units:

unitless

Count:

96

Description: Thermal ILC modbus address.

xPosition

IDL_Type:

float

Units:

unitless

Count:

96

Description: Fan x position.

yPosition

IDL_Type:

float

Units:

unitless

Count:

96

Description: Fan y position.

zPosition

IDL_Type:

float

Units:

unitless

Count:

96

Description: Fan z position.

ilcUniqueId

IDL_Type:

long long

Units:

unitless

Count:

96

Description: Thermal ILC unique id.

ilcApplicationType

IDL_Type:

short

Units:

unitless

Count:

96

Description: Thermal ILC application type. ILCType enumeration.

networkNodeType

IDL_Type:

short

Units:

unitless

Count:

96

Description: Thermal ILC network node type. ILCType enumeration. Mismatch with ilcApplicationType indicates ILC programming/seting problem.

majorRevision

IDL_Type:

short

Units:

unitless

Count:

96

Description: Thermal ILC major revision.

minorRevision

IDL_Type:

short

Units:

unitless

Count:

96

Description: Thermal ILC minor revision.

thermalSettings

Description: Thermal FCU settings.

EFDB_Topic:

MTM1M3TS_logevent_thermalSettings

enabledFCU

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: FCUs enabled/disabled in settings.

thermalWarning

Description: Thermal ILCs warnings.

EFDB_Topic:

MTM1M3TS_logevent_thermalWarning

anyWarning

IDL_Type:

boolean

Units:

unitless

Description: Does at least a single thermal fan unit indicates any warning?

anyMajorFault

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Major Fault.

majorFault

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning major Fault.

anyMinorFault

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Minor Fault.

minorFault

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning minor Fault.

anyFaultOverride

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Fault Override.

faultOverride

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning fault Override.

anyRefResistorError

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit any Ref Resistor Error.

refResistorError

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit Ref Resistor Error.

anyRTDError

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit any RTD Error.

rtdError

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit RTD Error.

anyBreakerHeater1Error

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit any Breaker Heater 1 Error.

breakerHeater1Error

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit Breaker Heater 1 Error.

anyBreakerFan2Error

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit any Breaker Fan 2 Error.

breakerFan2Error

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit Breaker Fan 2 Error.

anyUniqueIdCRCError

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Unique Id CRC Error.

uniqueIdCRCError

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning unique Id CRC Error.

anyApplicationTypeMismatch

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Application Type Mismatch.

applicationTypeMismatch

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning application Type Mismatch.

anyApplicationMissing

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Application Missing.

applicationMissing

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning application Missing.

anyApplicationCRCMismatch

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Application CRC Mismatch.

applicationCRCMismatch

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning application CRC Mismatch.

anyOneWireMissing

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any OneWire Missing.

oneWireMissing

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning oneWire Missing.

anyOneWire1Mismatch

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any OneWire1 Mismatch.

oneWire1Mismatch

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning oneWire1 Mismatch.

anyOneWire2Mismatch

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any OneWire2 Mismatch.

oneWire2Mismatch

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning oneWire2 Mismatch.

anyWatchdogReset

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Watchdog Rese.

watchdogReset

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning watchdog Reset.

anyBrownOut

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Brownout.

brownOut

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning brownout.

anyEventTrapReset

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Event Trap Reset.

eventTrapReset

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning event Trap Reset.

anySSRPowerFault

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any SSR Power Fault.

ssrPowerFault

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning SSR Power Fault.

anyAuxPowerFault

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Aux Power Fault.

auxPowerFault

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning aux Power Fault.

anyILCFault

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any ILC Fault.

ilcFault

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Force actuator warning ILC Fault.

anyBroadcastCounterWarning

IDL_Type:

boolean

Units:

unitless

Description: Thermal fan unit warning any Broadcast Counter Warning.

broadcastCounterWarning

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Thermal fan unit warning broadcast Counter Warning.

configurationApplied

Description: Information about this CSC’s current configuration overrides.

EFDB_Topic:

SALGeneric_logevent_configurationApplied

Category:

configurable

configurations

IDL_Type:

string

Units:

unitless

Description: A comma-separated list of configurations applied. If configuration comes from a clone of a git repo, or similar directory, then it will be a list of file names, without the file extension. Ignore whitespace after commas.

version

IDL_Type:

string

Units:

unitless

Description: Version of the configuration source. For a clone of a git repo it will be a git hash.

url

IDL_Type:

string

Units:

unitless

Description: URL of the configuration source. For a clone of a git repo this will be a file URL. For a database it will be a standard database URL. This should always match the same-named field in configurationsAvailable.

schemaVersion

IDL_Type:

string

Units:

unitless

Description: Version of config schema used by this CSC. For a configuration git repo, this is the name of a folder in the config package, and is typically something like “v1”. This should always match the same-named field in configurationsAvailable.

otherInfo

IDL_Type:

string

Units:

unitless

Description: A comma-separated list of event topics (without the logevent prefix) used to publish the entire set of configuration parameters loaded by this CSC, and any other pertinent information. Ignore whitespace after commas.

configurationsAvailable

Description: Available configuration overrides for this CSC.

EFDB_Topic:

SALGeneric_logevent_configurationsAvailable

Category:

configurable

overrides

IDL_Type:

string

Units:

unitless

Description: Available overrides as a comma-separated list. Each entry is a possible value of the configurationOverride field of the start command. Ignore whitespace after commas.

version

IDL_Type:

string

Units:

unitless

Description: Version of the configuration source. For a clone of a git repo it will be a git hash.

url

IDL_Type:

string

Units:

unitless

Description: URL of the configuration source. For a clone of a git repo this will be a file URL. For a database it will be a standard database URL.

schemaVersion

IDL_Type:

string

Units:

unitless

Description: Version of config schema used by this CSC. For a configuration git repo, this is the name of a folder in the config package, and is typically something like “v1”.

errorCode

Description: Output when this CSC goes into the Fault state as an explanation of the problem.

EFDB_Topic:

SALGeneric_logevent_errorCode

Category:

csc

errorCode

IDL_Type:

long

Units:

unitless

Description: A numeric error code.

errorReport

IDL_Type:

string

Units:

unitless

Description: An string providing detailed information about the error.

traceback

IDL_Type:

string

Units:

unitless

Description: An optional stack trace of the error condition.

heartbeat

Description: Event output at regular intervals (typcally once per second) to show that the SAL component is alive.

EFDB_Topic:

SALGeneric_logevent_heartbeat

Category:

mandatory

heartbeat

IDL_Type:

boolean

Units:

unitless

Description: Deprecated field that you should ignore.

logLevel

Description: Current logging level.

EFDB_Topic:

SALGeneric_logevent_logLevel

Category:

mandatory

level

IDL_Type:

int

Units:

unitless

Description: Current logging level, a Python logging level: error=40, warning=30, info=20, debug=10.

subsystem

IDL_Type:

string

Units:

unitless

Description: If this CSC itself has sub-ordinate components, they may be listed here. An empty string means the setting applies to all such sub-ordinate components, or just to this CSC itself.

logMessage

Description: A log message.

EFDB_Topic:

SALGeneric_logevent_logMessage

Category:

mandatory

name

IDL_Type:

string

Units:

unitless

Description: Log name.

level

IDL_Type:

int

Units:

unitless

Description: Message level, a Python logging level: error=40, warning=30, info=20, debug=10.

message

IDL_Type:

string

Units:

unitless

Description: Log message.

traceback

IDL_Type:

string

Units:

unitless

Description: Exception traceback; “” if not an exception.

filePath

IDL_Type:

string

Units:

unitless

Description: Path to source file.

functionName

IDL_Type:

string

Units:

unitless

Description: Function or method name.

lineNumber

IDL_Type:

long

Units:

unitless

Description: Line number in the file specified by filePath.

process

IDL_Type:

long

Units:

unitless

Description: Process ID.

timestamp

IDL_Type:

double

Units:

second

Description: The time at which the condition being reported was observed (TAI unix seconds). 0 if unspecified.

simulationMode

Description: Current simulation mode.

EFDB_Topic:

SALGeneric_logevent_simulationMode

Category:

csc

mode

IDL_Type:

int

Units:

unitless

Description: Current simulation mode; 0 for normal operation (no simulation); other supported values are specific to each CSC.

softwareVersions

Description: Current versions of software in use by CSC.

EFDB_Topic:

SALGeneric_logevent_softwareVersions

Category:

mandatory

salVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: This is the current version of SAL generation.

xmlVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: This is the current version of CSC XML.

openSpliceVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: This is the current version of OpenSplice.

cscVersion

IDL_Type:

string

IDL_Size:

256

Units:

unitless

Description: The software version of this CSC.

subsystemVersions

IDL_Type:

string

Units:

unitless

Description: A comma delimited list of key=value pairs relating subsystem name (key) to its version number (value). This may be left blank if there are no subsystems within this CSC.

summaryState

Description: Current summary state of this CSC.

EFDB_Topic:

SALGeneric_logevent_summaryState

Category:

csc

summaryState

IDL_Type:

long

Units:

unitless

Description: High level state machine state identifier.

Telemetry

flowMeter

Description: Flow meter telemetry.

EFDB_Topic:

MTM1M3TS_flowMeter

signalStrength

IDL_Type:

float

Units:

unitless

Description: Flow meter signal strength. Values > 5 signal good signal reception.

flowRate

IDL_Type:

float

Units:

liter/minute

Description: Current flow rate measured by the flow meter

netTotalizer

IDL_Type:

float

Units:

liter

Description: Total flow.

positiveTotalizer

IDL_Type:

float

Units:

liter

Description: Total positive flow.

negativeTotalizer

IDL_Type:

float

Units:

liter

Description: Total negative flow.

glycolLoopTemperature

Description: Glycol loop temperature, measured by Thermal Sensors.

EFDB_Topic:

MTM1M3TS_glycolLoopTemperature

aboveMirrorTemperature

IDL_Type:

float

Units:

deg_C

Description: Air temperature measured above mirror level by sensor TS1-A.

insideCellTemperature1

IDL_Type:

float

Units:

deg_C

Description: Cell temperature measured inside mirror cell by sensor TS2-MC.

insideCellTemperature2

IDL_Type:

float

Units:

deg_C

Description: Cell temperature measured inside mirror cell by sensor TS3-MC.

insideCellTemperature3

IDL_Type:

float

Units:

deg_C

Description: Cell temperature measured inside mirror cell by sensor TS4-MC.

telescopeCoolantSupplyTemperature

IDL_Type:

float

Units:

deg_C

Description: Temperature of input glycol (flowing from telescope/chillers), sensor TS5-G.

telescopeCoolantReturnTemperature

IDL_Type:

float

Units:

deg_C

Description: Temperature of returned glycol (returning to chillers), sensor TS6-G.

mirrorCoolantSupplyTemperature

IDL_Type:

float

Units:

deg_C

Description: Temperature of mirror glycol loop supply (measured after mixing valve), sensor TS7-G.

mirrorCoolantReturnTemperature

IDL_Type:

float

Units:

deg_C

Description: Temperature of mirror glycol loop return (measured before mixing valve), sensor TS8-G.

glycolPump

Description: Telemetry from glycol pump.

EFDB_Topic:

MTM1M3TS_glycolPump

commandedFrequency

IDL_Type:

float

Units:

Hz

Description: Commanded frequency.

targetFrequency

IDL_Type:

float

Units:

Hz

Description: Pump motor target frequency.

outputFrequency

IDL_Type:

float

Units:

Hz

Description: Pump motor output (measured) frequency.

outputCurrent

IDL_Type:

float

Units:

A

Description: Pump motor output (measured) current.

busVoltage

IDL_Type:

float

Units:

V

Description: Pump motor DC bus voltage.

outputVoltage

IDL_Type:

float

Units:

V

Description: Pump motor output (measured) voltage.

mixingValve

Description: Mixing valve position.

EFDB_Topic:

MTM1M3TS_mixingValve

rawValvePosition

IDL_Type:

float

Units:

V

Description: Mixing valve measured raw position.

valvePosition

IDL_Type:

float

Units:

%

Description: Mixing valve measured position.

thermalData

Description: Thermal status response data. Return of ILC command 89 (0x59).

EFDB_Topic:

MTM1M3TS_thermalData

timestamp

IDL_Type:

double

Units:

second

Description: Timestamp the data was generated (TAI unix seconds).

ilcFault

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: ILC Fault.

heaterDisabled

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Heater disabled.

heaterBreaker

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Heater circuit breaker (false=closed/OK, true=open/tripped).

fanBreaker

IDL_Type:

boolean

Units:

unitless

Count:

96

Description: Fan circuit breaker (false=closed/OK, true=open/tripped).

differentialTemperature

IDL_Type:

float

Units:

deg_C

Count:

96

Description: Differential temperature.

fanRPM

IDL_Type:

unsigned short

Units:

unitless

Count:

96

Description: Measured fan RPM-0 to 2550 RPM.

absoluteTemperature

IDL_Type:

float

Units:

deg_C

Count:

96

Description: Absolute temperature.