MTM1M3TS¶
Note
This page is generated by python script generate_cet.py
.
Commands¶
applySetpoint¶
Description: Set new setpoint target for mirror temperature.
- EFDB_Topic:
MTM1M3TS_command_applySetpoint
setpoint¶
- IDL_Type:
float
- Units:
deg_C
Description: Temperature setpoint to apply
coolantPumpFrequency¶
- Description:
Sets coolant pump target frequency. 0 or negative values stops the pump. Pump is started if positive value is provided and it’s not running.
- EFDB_Topic:
MTM1M3TS_command_coolantPumpFrequency
targetFrequency¶
- IDL_Type:
float
- Units:
Hz
Description: Coolant pump target frequency.
coolantPumpPower¶
Description: Turns power for coolant pump. Controls cRIO slot 5 SSR.
- EFDB_Topic:
MTM1M3TS_command_coolantPumpPower
power¶
- IDL_Type:
boolean
- Units:
unitless
Description: Apply power to coolant pump, true=on, false=off.i Slot 5, Channel 2.
coolantPumpReset¶
Description: Resets coolant pump motor controller errors.
- EFDB_Topic:
MTM1M3TS_command_coolantPumpReset
coolantPumpStart¶
Description: Start (run) the glycol coolant pump.
- EFDB_Topic:
MTM1M3TS_command_coolantPumpStart
coolantPumpStop¶
Description: Stops the glycol coolant pump.
- EFDB_Topic:
MTM1M3TS_command_coolantPumpStop
fanCoilsHeatersPower¶
Description: Turns power for fan coils/heaters. Controls cRIO slot 5 SSR.
- EFDB_Topic:
MTM1M3TS_command_fanCoilsHeatersPower
power¶
- IDL_Type:
boolean
- Units:
unitless
Description: Apply power to Fan Coils/Heaters. true=on, false=off. Slot 5, Channel 0
heaterFanDemand¶
Description: Sets thermal unit heater PWM and fan RPM demand values. Command code 88 (0x58).
- EFDB_Topic:
MTM1M3TS_command_heaterFanDemand
heaterPWM¶
- IDL_Type:
byte
- Units:
unitless
- Count:
96
Description: Heater PWM demand. 0-255, where 255 equals 100%.
fanRPM¶
- IDL_Type:
byte
- Units:
unitless
- Count:
96
Description: Fan RPM demand value. 0-255, where 255 equals 2550 RPM.
setEngineeringMode¶
Description: Enters and leaves engineering mode.
- EFDB_Topic:
MTM1M3TS_command_setEngineeringMode
enableEngineeringMode¶
- IDL_Type:
boolean
- Units:
unitless
Description: Enable engineering mode.
setMixingValve¶
Description: Sets mixing valve position. Controls AO0 at slot 2.
- EFDB_Topic:
MTM1M3TS_command_setMixingValve
mixingValveTarget¶
- IDL_Type:
float
- Units:
%
Description: Mixing valve commanded position.
disable¶
Description: Transition from state Enabled to Disabled.
- EFDB_Topic:
SALGeneric_command_disable
- Category:
csc
enable¶
Description: Transition from state Disabled to Enabled.
- EFDB_Topic:
SALGeneric_command_enable
- Category:
csc
exitControl¶
Description: Transition from state Standby to Offline. Most CSCs will quit, but CSCs that support the enterControl command will keep running.
- EFDB_Topic:
SALGeneric_command_exitControl
- Category:
csc
setLogLevel¶
Description: Set the logging level.
- EFDB_Topic:
SALGeneric_command_setLogLevel
- Category:
csc
level¶
- IDL_Type:
int
- Units:
unitless
Description: Logging level, as a Python logging level: error=40, warning=30, info=20, debug=10.
subsystem¶
- IDL_Type:
string
- Units:
unitless
Description: If this CSC itself has sub-ordinate components, they may be listed here. An empty string means the setting applies to all such sub-ordinate components, or just to this CSC itself.
standby¶
Description: Transition from state Offline/Available, Disabled or Fault to Standby.
- EFDB_Topic:
SALGeneric_command_standby
- Category:
csc
start¶
Description: Transition from state Standby to Disable, in a specified configuration.
- EFDB_Topic:
SALGeneric_command_start
- Category:
csc
configurationOverride¶
- IDL_Type:
string
- Units:
unitless
- Description:
Configuration override in the form [{name}][:{version}]. For salobj-based CSCs: name is a filename with “.yaml” suffix and version is a git hash; for example:
“foo.yaml” specifies just a file. Two or three config files are loaded: “_init.yaml”, “_{site}.yaml” (if present), and “foo.yaml”.
“:37bf936” specifies just a git hash. One or two config files are loaded from the specified git commit: “_init.yaml” and “_{site}.yaml” (if present.
“bar.yaml:HEAD~2” specifies both a file and a git hash. Two or three config files are read from the specified git commit: “_init.yaml”, “_{site}.yaml” (if present), and “bar.yaml”.
Enumerations¶
- SummaryStates:
DisabledState=1
EnabledState=2
FaultState=3
OfflineState=4
StandbyState=5
Events¶
appliedSetpoint¶
Description: Current target temperature setpoint.
- EFDB_Topic:
MTM1M3TS_logevent_appliedSetpoint
setpoint¶
- IDL_Type:
float
- Units:
deg_C
Description: Applied setpoint.
enabledILC¶
Description: Currently enabled ILCs.
- EFDB_Topic:
MTM1M3TS_logevent_enabledILC
enabled¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: True if this fan unit is enabled.
engineeringMode¶
Description: Is the system in engineering mode, allowing wider range of commands than non-engineering mode?
- EFDB_Topic:
MTM1M3TS_logevent_engineeringMode
engineeringMode¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if engineering mode is engaged.
flowMeterMPUStatus¶
Description: Flow meter MPU status and warnings. Send when errors are detected.
- EFDB_Topic:
MTM1M3TS_logevent_flowMeterMPUStatus
instructionPointer¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU instruction pointer.
outputCounter¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU output counter.
inputCounter¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU input counter.
outputTimeouts¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU output timeouts counter.
inputTimeouts¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU input timeouts counter.
instructionPointerOnError¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU instruction pointer when error was detected.
writeTimeout¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU write timeout.
readTimeout¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU read timeout.
errorCode¶
- IDL_Type:
int
- Units:
unitless
Description: MPU error code.
glycolPumpMPUStatus¶
Description: Glycol pump MPU status and warnings. Send when errors are detected.
- EFDB_Topic:
MTM1M3TS_logevent_glycolPumpMPUStatus
instructionPointer¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU instruction pointer.
outputCounter¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU output counter.
inputCounter¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU input counter.
outputTimeouts¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU output timeouts counter.
inputTimeouts¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU input timeouts counter.
instructionPointerOnError¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU instruction pointer when error was detected.
writeTimeout¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU write timeout.
readTimeout¶
- IDL_Type:
int
- Units:
unitless
Description: Current MPU read timeout.
errorCode¶
- IDL_Type:
int
- Units:
unitless
Description: MPU error code.
glycolPumpStatus¶
Description: Glycol pump status.
- EFDB_Topic:
MTM1M3TS_logevent_glycolPumpStatus
ready¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if the pump can be started.
running¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if the pump is running.
forwardCommanded¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if pump motor is commanded to run forward, false for backward command.
forwardRotating¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if pump motor is rotating forward, false for backward rotation.
accelerating¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if motor is accelerating.
decelerating¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if motor is decelerating.
faulted¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if motor faulted.
mainFrequencyControlled¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if main frequency is controlled by the active communication.
operationCommandControlled¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if pump motor operation is controlled by the active communication.
parametersLocked¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if pump motor parameters are locked.
errorCode¶
- IDL_Type:
int
- Units:
unitless
Description: Motor controller error code. Please see VFD documentation for details.
mixingValveSettings¶
Description: Mixing Valve settings.
- EFDB_Topic:
MTM1M3TS_logevent_mixingValveSettings
commandingFullyClosed¶
- IDL_Type:
float
- Units:
mA
Description: Raw value at which is mixing valve fully closed.
commandingFullyOpened¶
- IDL_Type:
float
- Units:
mA
Description: Raw value at which is mixing valve fully opened.
positionFeedbackFullyClosed¶
- IDL_Type:
float
- Units:
V
Description: Voltage level signalling fully closed mixing valve.
positionFeedbackFullyOpened¶
- IDL_Type:
float
- Units:
V
Description: Voltage level signalling fully opened mixing valve.
powerStatus¶
Description: Power status.
- EFDB_Topic:
MTM1M3TS_logevent_powerStatus
fanCoilsHeatersCommandedOn¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if Fan Coils/Heaters power bus commanded on.
fanCoilsHeatersOn¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if Fan Coils/Heaters are on.
coolantPumpCommandedOn¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if Coolant Pump commanded on.
coolantPumpOn¶
- IDL_Type:
boolean
- Units:
unitless
Description: True if Coolant Pump is on.
thermalInfo¶
Description: ILC information - position, address,..
- EFDB_Topic:
MTM1M3TS_logevent_thermalInfo
referenceId¶
- IDL_Type:
short
- Units:
unitless
- Count:
96
Description: Thermal ILC reference id.
modbusAddress¶
- IDL_Type:
short
- Units:
unitless
- Count:
96
Description: Thermal ILC modbus address.
xPosition¶
- IDL_Type:
float
- Units:
unitless
- Count:
96
Description: Fan x position.
yPosition¶
- IDL_Type:
float
- Units:
unitless
- Count:
96
Description: Fan y position.
zPosition¶
- IDL_Type:
float
- Units:
unitless
- Count:
96
Description: Fan z position.
ilcUniqueId¶
- IDL_Type:
long long
- Units:
unitless
- Count:
96
Description: Thermal ILC unique id.
ilcApplicationType¶
- IDL_Type:
short
- Units:
unitless
- Count:
96
Description: Thermal ILC application type. ILCType enumeration.
networkNodeType¶
- IDL_Type:
short
- Units:
unitless
- Count:
96
Description: Thermal ILC network node type. ILCType enumeration. Mismatch with ilcApplicationType indicates ILC programming/seting problem.
majorRevision¶
- IDL_Type:
short
- Units:
unitless
- Count:
96
Description: Thermal ILC major revision.
minorRevision¶
- IDL_Type:
short
- Units:
unitless
- Count:
96
Description: Thermal ILC minor revision.
thermalSettings¶
Description: Thermal FCU settings.
- EFDB_Topic:
MTM1M3TS_logevent_thermalSettings
enabledFCU¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: FCUs enabled/disabled in settings.
thermalWarning¶
Description: Thermal ILCs warnings.
- EFDB_Topic:
MTM1M3TS_logevent_thermalWarning
anyWarning¶
- IDL_Type:
boolean
- Units:
unitless
Description: Does at least a single thermal fan unit indicates any warning?
anyMajorFault¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Major Fault.
majorFault¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning major Fault.
anyMinorFault¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Minor Fault.
minorFault¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning minor Fault.
anyFaultOverride¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Fault Override.
faultOverride¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning fault Override.
anyRefResistorError¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit any Ref Resistor Error.
refResistorError¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit Ref Resistor Error.
anyRTDError¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit any RTD Error.
rtdError¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit RTD Error.
anyBreakerHeater1Error¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit any Breaker Heater 1 Error.
breakerHeater1Error¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit Breaker Heater 1 Error.
anyBreakerFan2Error¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit any Breaker Fan 2 Error.
breakerFan2Error¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit Breaker Fan 2 Error.
anyUniqueIdCRCError¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Unique Id CRC Error.
uniqueIdCRCError¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning unique Id CRC Error.
anyApplicationTypeMismatch¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Application Type Mismatch.
applicationTypeMismatch¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning application Type Mismatch.
anyApplicationMissing¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Application Missing.
applicationMissing¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning application Missing.
anyApplicationCRCMismatch¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Application CRC Mismatch.
applicationCRCMismatch¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning application CRC Mismatch.
anyOneWireMissing¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any OneWire Missing.
oneWireMissing¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning oneWire Missing.
anyOneWire1Mismatch¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any OneWire1 Mismatch.
oneWire1Mismatch¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning oneWire1 Mismatch.
anyOneWire2Mismatch¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any OneWire2 Mismatch.
oneWire2Mismatch¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning oneWire2 Mismatch.
anyWatchdogReset¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Watchdog Rese.
watchdogReset¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning watchdog Reset.
anyBrownOut¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Brownout.
brownOut¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning brownout.
anyEventTrapReset¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Event Trap Reset.
eventTrapReset¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning event Trap Reset.
anySSRPowerFault¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any SSR Power Fault.
ssrPowerFault¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning SSR Power Fault.
anyAuxPowerFault¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Aux Power Fault.
auxPowerFault¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning aux Power Fault.
anyILCFault¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any ILC Fault.
ilcFault¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Force actuator warning ILC Fault.
anyBroadcastCounterWarning¶
- IDL_Type:
boolean
- Units:
unitless
Description: Thermal fan unit warning any Broadcast Counter Warning.
broadcastCounterWarning¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Thermal fan unit warning broadcast Counter Warning.
configurationApplied¶
Description: Information about this CSC’s current configuration overrides.
- EFDB_Topic:
SALGeneric_logevent_configurationApplied
- Category:
configurable
configurations¶
- IDL_Type:
string
- Units:
unitless
Description: A comma-separated list of configurations applied. If configuration comes from a clone of a git repo, or similar directory, then it will be a list of file names, without the file extension. Ignore whitespace after commas.
version¶
- IDL_Type:
string
- Units:
unitless
Description: Version of the configuration source. For a clone of a git repo it will be a git hash.
url¶
- IDL_Type:
string
- Units:
unitless
Description: URL of the configuration source. For a clone of a git repo this will be a file URL. For a database it will be a standard database URL. This should always match the same-named field in configurationsAvailable.
schemaVersion¶
- IDL_Type:
string
- Units:
unitless
Description: Version of config schema used by this CSC. For a configuration git repo, this is the name of a folder in the config package, and is typically something like “v1”. This should always match the same-named field in configurationsAvailable.
otherInfo¶
- IDL_Type:
string
- Units:
unitless
Description: A comma-separated list of event topics (without the logevent prefix) used to publish the entire set of configuration parameters loaded by this CSC, and any other pertinent information. Ignore whitespace after commas.
configurationsAvailable¶
Description: Available configuration overrides for this CSC.
- EFDB_Topic:
SALGeneric_logevent_configurationsAvailable
- Category:
configurable
overrides¶
- IDL_Type:
string
- Units:
unitless
Description: Available overrides as a comma-separated list. Each entry is a possible value of the configurationOverride
field of the start
command. Ignore whitespace after commas.
version¶
- IDL_Type:
string
- Units:
unitless
Description: Version of the configuration source. For a clone of a git repo it will be a git hash.
url¶
- IDL_Type:
string
- Units:
unitless
Description: URL of the configuration source. For a clone of a git repo this will be a file URL. For a database it will be a standard database URL.
schemaVersion¶
- IDL_Type:
string
- Units:
unitless
Description: Version of config schema used by this CSC. For a configuration git repo, this is the name of a folder in the config package, and is typically something like “v1”.
errorCode¶
Description: Output when this CSC goes into the Fault state as an explanation of the problem.
- EFDB_Topic:
SALGeneric_logevent_errorCode
- Category:
csc
errorCode¶
- IDL_Type:
long
- Units:
unitless
Description: A numeric error code.
errorReport¶
- IDL_Type:
string
- Units:
unitless
Description: An string providing detailed information about the error.
traceback¶
- IDL_Type:
string
- Units:
unitless
Description: An optional stack trace of the error condition.
heartbeat¶
Description: Event output at regular intervals (typcally once per second) to show that the SAL component is alive.
- EFDB_Topic:
SALGeneric_logevent_heartbeat
- Category:
mandatory
heartbeat¶
- IDL_Type:
boolean
- Units:
unitless
Description: Deprecated field that you should ignore.
logLevel¶
Description: Current logging level.
- EFDB_Topic:
SALGeneric_logevent_logLevel
- Category:
mandatory
level¶
- IDL_Type:
int
- Units:
unitless
Description: Current logging level, a Python logging level: error=40, warning=30, info=20, debug=10.
subsystem¶
- IDL_Type:
string
- Units:
unitless
Description: If this CSC itself has sub-ordinate components, they may be listed here. An empty string means the setting applies to all such sub-ordinate components, or just to this CSC itself.
logMessage¶
Description: A log message.
- EFDB_Topic:
SALGeneric_logevent_logMessage
- Category:
mandatory
name¶
- IDL_Type:
string
- Units:
unitless
Description: Log name.
level¶
- IDL_Type:
int
- Units:
unitless
Description: Message level, a Python logging level: error=40, warning=30, info=20, debug=10.
message¶
- IDL_Type:
string
- Units:
unitless
Description: Log message.
traceback¶
- IDL_Type:
string
- Units:
unitless
Description: Exception traceback; “” if not an exception.
filePath¶
- IDL_Type:
string
- Units:
unitless
Description: Path to source file.
functionName¶
- IDL_Type:
string
- Units:
unitless
Description: Function or method name.
lineNumber¶
- IDL_Type:
long
- Units:
unitless
Description: Line number in the file specified by filePath.
process¶
- IDL_Type:
long
- Units:
unitless
Description: Process ID.
timestamp¶
- IDL_Type:
double
- Units:
second
Description: The time at which the condition being reported was observed (TAI unix seconds). 0 if unspecified.
simulationMode¶
Description: Current simulation mode.
- EFDB_Topic:
SALGeneric_logevent_simulationMode
- Category:
csc
mode¶
- IDL_Type:
int
- Units:
unitless
Description: Current simulation mode; 0 for normal operation (no simulation); other supported values are specific to each CSC.
softwareVersions¶
Description: Current versions of software in use by CSC.
- EFDB_Topic:
SALGeneric_logevent_softwareVersions
- Category:
mandatory
salVersion¶
- IDL_Type:
string
- IDL_Size:
256
- Units:
unitless
Description: This is the current version of SAL generation.
xmlVersion¶
- IDL_Type:
string
- IDL_Size:
256
- Units:
unitless
Description: This is the current version of CSC XML.
openSpliceVersion¶
- IDL_Type:
string
- IDL_Size:
256
- Units:
unitless
Description: This is the current version of OpenSplice.
cscVersion¶
- IDL_Type:
string
- IDL_Size:
256
- Units:
unitless
Description: The software version of this CSC.
subsystemVersions¶
- IDL_Type:
string
- Units:
unitless
Description: A comma delimited list of key=value pairs relating subsystem name (key) to its version number (value). This may be left blank if there are no subsystems within this CSC.
summaryState¶
Description: Current summary state of this CSC.
- EFDB_Topic:
SALGeneric_logevent_summaryState
- Category:
csc
summaryState¶
- IDL_Type:
long
- Units:
unitless
Description: High level state machine state identifier.
Telemetry¶
flowMeter¶
Description: Flow meter telemetry.
- EFDB_Topic:
MTM1M3TS_flowMeter
signalStrength¶
- IDL_Type:
float
- Units:
unitless
Description: Flow meter signal strength. Values > 5 signal good signal reception.
flowRate¶
- IDL_Type:
float
- Units:
liter/minute
Description: Current flow rate measured by the flow meter
netTotalizer¶
- IDL_Type:
float
- Units:
liter
Description: Total flow.
positiveTotalizer¶
- IDL_Type:
float
- Units:
liter
Description: Total positive flow.
negativeTotalizer¶
- IDL_Type:
float
- Units:
liter
Description: Total negative flow.
glycolLoopTemperature¶
Description: Glycol loop temperature, measured by Thermal Sensors.
- EFDB_Topic:
MTM1M3TS_glycolLoopTemperature
aboveMirrorTemperature¶
- IDL_Type:
float
- Units:
deg_C
Description: Air temperature measured above mirror level by sensor TS1-A.
insideCellTemperature1¶
- IDL_Type:
float
- Units:
deg_C
Description: Cell temperature measured inside mirror cell by sensor TS2-MC.
insideCellTemperature2¶
- IDL_Type:
float
- Units:
deg_C
Description: Cell temperature measured inside mirror cell by sensor TS3-MC.
insideCellTemperature3¶
- IDL_Type:
float
- Units:
deg_C
Description: Cell temperature measured inside mirror cell by sensor TS4-MC.
telescopeCoolantSupplyTemperature¶
- IDL_Type:
float
- Units:
deg_C
Description: Temperature of input glycol (flowing from telescope/chillers), sensor TS5-G.
telescopeCoolantReturnTemperature¶
- IDL_Type:
float
- Units:
deg_C
Description: Temperature of returned glycol (returning to chillers), sensor TS6-G.
mirrorCoolantSupplyTemperature¶
- IDL_Type:
float
- Units:
deg_C
Description: Temperature of mirror glycol loop supply (measured after mixing valve), sensor TS7-G.
mirrorCoolantReturnTemperature¶
- IDL_Type:
float
- Units:
deg_C
Description: Temperature of mirror glycol loop return (measured before mixing valve), sensor TS8-G.
glycolPump¶
Description: Telemetry from glycol pump.
- EFDB_Topic:
MTM1M3TS_glycolPump
commandedFrequency¶
- IDL_Type:
float
- Units:
Hz
Description: Commanded frequency.
targetFrequency¶
- IDL_Type:
float
- Units:
Hz
Description: Pump motor target frequency.
outputFrequency¶
- IDL_Type:
float
- Units:
Hz
Description: Pump motor output (measured) frequency.
outputCurrent¶
- IDL_Type:
float
- Units:
A
Description: Pump motor output (measured) current.
busVoltage¶
- IDL_Type:
float
- Units:
V
Description: Pump motor DC bus voltage.
outputVoltage¶
- IDL_Type:
float
- Units:
V
Description: Pump motor output (measured) voltage.
mixingValve¶
Description: Mixing valve position.
- EFDB_Topic:
MTM1M3TS_mixingValve
rawValvePosition¶
- IDL_Type:
float
- Units:
V
Description: Mixing valve measured raw position.
valvePosition¶
- IDL_Type:
float
- Units:
%
Description: Mixing valve measured position.
thermalData¶
Description: Thermal status response data. Return of ILC command 89 (0x59).
- EFDB_Topic:
MTM1M3TS_thermalData
timestamp¶
- IDL_Type:
double
- Units:
second
Description: Timestamp the data was generated (TAI unix seconds).
ilcFault¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: ILC Fault.
heaterDisabled¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Heater disabled.
heaterBreaker¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Heater circuit breaker (false=closed/OK, true=open/tripped).
fanBreaker¶
- IDL_Type:
boolean
- Units:
unitless
- Count:
96
Description: Fan circuit breaker (false=closed/OK, true=open/tripped).
differentialTemperature¶
- IDL_Type:
float
- Units:
deg_C
- Count:
96
Description: Differential temperature.
fanRPM¶
- IDL_Type:
unsigned short
- Units:
unitless
- Count:
96
Description: Measured fan RPM-0 to 2550 RPM.
absoluteTemperature¶
- IDL_Type:
float
- Units:
deg_C
- Count:
96
Description: Absolute temperature.